Fault Description | System Behaviour |
---|---|
200 O | Boiler in heating mode |
201 O | Boiler in hot water mode |
202 O | Boiler in anti-cycle mode |
203 0 | Boiler in standby – no heat energy demand |
204 O | Current primary water temperature higher than set value |
208 0 | Chimney sweep demand |
224 V | Safety temperature limiter has tripped – top-up water until the reset pressure is reached |
227 V | No flame signal after ignition burner control unit could need replacing |
228 V | Flame signal without flame present – air/gas ratio control valve may need replacing as might the ionisation cable |
305 0 | Boiler in hot water anti-cycle mode |
306 V | Flame signal after closing the fuel supply – the air/gas ratio control valve might need replacing |
360 V | Incompatible code plug – check if a correct code plug is installed and exchange or reconnect code plug |
815 W/B | Low loss header temperature sensor faulty – check the sensor port or check the differential sensor for incorrect installation position or breakage |
1010 O | No BUS communication cable, EMS-Bus isn’t connected or damaged – connect the cable for the EMS-Bus or replace the damaged cable exchange fuse |
1017 W | Water pressure too low – the water needs topping up and the vent system or pressure sensor may need replacing |
1021 B | Hot water temperature sensor is defective – the plug to the hot water temperature sensor may not be connected |
1022 B | Hot water storage temperature sensor is defective – connect the plug to the hot water temperature sensor correctly, mount the hot water temperature sensor correctly or replace the hot water temperature sensor |
1037 W | Outside temperature sensor is defective – check the connecting lead |
1065 B | Pressure sensor defective or not connected – check pressure sensor connection as it may need replacing |
1068 W | Outside temperature sensor defective – check the connecting lead |
1073 W | Short circuit of the flow temperature sensor – the temperature sensor may need replacing |
1074 W | No signal from the flow temperature sensor available – connect the plug to the flow temperature sensor correctly or temperature sensor could need replacing |
1075 W | Short circuit of the temperature sensor at the heating block – temperature sensor may need replacing |
1076 W | No signal from the temperature sensor at the heating block available – replace the temperature sensor, the connecting lead or the control unit |
2920 V | Error with the flame monitoring |
2924 V | No feedback from the modulating gas valve. The gas valve relay is defective – press the reset button and apply burner start, wait to see if fault reoccurs, if it does the gas valve needs replacing |
2925 V | Feedback from the modulating gas valve is too low |
2927 B | Flame failed during burner operation. Open the main shut off valve, shut down the appliance and check gas line, replace the ionisation electrode, set burner correctly and minimum rated load, check the integrity flue system and if the interconnected room air supply is too small, or the size of the ventilation opening is too small, clean the heating block on the flue gas side or replace the control unit/burner control unit |
2946 V | Incorrect code plug detected – the code plug needs replacing |
2948 B | No flame signal. With low output the burner starts automatically after cleaning. If the fault occurs repeatedly, the setting of the CO2 valves need checking |
2950 B | No flame signal. Following starting procedure the burner starts automatically. After cleaning set the correct gas / air ratio correctly |
2963 B | Signal from flow and heat exchanger temperature sensor outside the permissible range – the connecting lead needs connecting correctly |
2964 B | Flow rate in heat exchanger is too low |
2965 B | Flow temperature too high |
2966 B | Flow temperature rise in heat exchanger too rapid |
2967 B | Flow / heat exchanger temperature sensor differential too great |
2970 B | Pressure drop in heating system too rapid |
2971 B | System pressure too low – the heating system needs venting or water needs topping up until the preset pressure is reached. Replace the cable to the pressure sensor replace the pressure sensor |